Showing 5113–5124 of 18231 results
-
Product Name: Inverter.
Model: ACS800-01-0030-5.
UN ACS800-01-0030-5 = 500 V (Range 380 to 500 V). The power ratings are valid at ACS800-01-0030-5 nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 42A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 62A.
Typical motor power in no-overload use: 22KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 39A.
Frame size: R4.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 32A.
Typical motor power in heavy-duty use: 18.5KW.
Typical motor power in light-overload use: 22Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0030-7 ACS800-01-0030-7.
UN = 690 V (Range 525 to 690 V). The power ACS800-01-0030-7 ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 33A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 44A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 30A.
Frame size: R4.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 22A.
Typical motor power in heavy-duty use: 18.5KW.
Typical motor power in light-overload use: 22Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0040-2.
UN ACS800-01-0040-2 = 230 V (Range 208 to 240 V). The power ratings are valid at ACS800-01-0040-2 nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 103A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 94A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
Typical motor power in heavy-duty use: 18.5KW.
Frame size: R5.
Typical motor power in light-overload use: 22Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0040-3.
UN ACS800-01-0040-3 = 400 V (Range 380 to 415 V). The power ratings are valid at ACS800-01-0040-3 nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 72A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 37KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 69A.
Typical motor power in light-overload use: 30Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in heavy-duty use: 22KW.
Frame size: R5.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 49A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0040-5.
UN ACS800-01-0040-5 = 500 V (Range 380 to 500 V). The power ratings are valid at ACS800-01-0040-5 nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 48A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 72A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 44A.
Typical motor power in light-overload use: 30Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 36A.
Typical motor power in heavy-duty use: 22KW.
Frame size: R4.
Typical motor power in no-overload use: 30KW
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0040-7.
UN ACS800-01-0030-7 = 690 V (Range 525 to 690 V). The power ratings are valid at ACS800-01-0030-7 nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 36A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 54A.
Typical motor power in no-overload use: 30KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in light-overload use: 30Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 27A.
Typical motor power in heavy-duty use: 22KW.
Frame size: R4.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 34A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0050-2.
UN ACS800-01-0050-2 = 230 V (Range 208 to 240 V). The power ratings are valid at ACS800-01-0050-2 nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 141A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 164A.
Typical motor power in no-overload use: 37KW
Frame size: R6.
Typical motor power in light-overload use: 37Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 97A.
Typical motor power in heavy-duty use: 30KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 132A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0050-3.
UN ACS800-01-0050-3 = 400 V (Range 380 to 415 V). The power ratings are valid at ACS800-01-0050-3 nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 86A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 112A.
Typical motor power in no-overload use: 45KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 80A.
Frame size: R5.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Typical motor power in heavy-duty use: 30KW.
Typical motor power in light-overload use: 37Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0050-5.
UN ACS800-01-0050-5 = 500 V (Range 380 to 500 V). The power ratings are valid at ACS800-01-0050-5 nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 65A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 37KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 61A.
Typical motor power in light-overload use: 37Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 30KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 50A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg. -
Product Name: Inverter.
Model: ACS800-01-0060-2.
UN ACS800-01-0060-2 = 230 V (Range 208 to 240 V). The power ratings are valid at ACS800-01-0060-2 nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 166A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 202A.
Typical motor power in no-overload use: 45KW
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 115A.
Typical motor power in heavy-duty use: 30KW.
Frame size: R6.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 155A. -
Product Name: Inverter.
Model: ACS800-01-0060-3.
UN ACS800-01-0060-3 = 400 V (Range 380 to 415 V). The power ratings are valid at ACS800-01-0060-3 nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 103A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in no-overload use: 55KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 94A.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 37KW. -
Product Name: Inverter.
Model: ACS800-01-0060-5.
UN ACS800-01-0060-5 = 500 V (Range 380 to 500 V). The power ratings are valid at ACS800-01-0060-5 nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 79A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 112A.
Typical motor power in no-overload use: 45KW
Frame size: R5.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Typical motor power in heavy-duty use: 37KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 75A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.