Description
Sensor Type:…
a ammonia 0-50 / 100 / 1000ppm b Oxygen 0-25% VOL
c chlorine 0-5 / 15ppm d sulfide 0-50 / 100ppm [123. ] e. carbon monoxide 0-100 / 200 / 500ppm f. hydrogen 0-1000 / 10000ppm
g. sulfur dioxide 0-15 / 50ppm h. nitric oxide (nitrogen oxides) 0-100 / 500ppm
i. nitrogen dioxide 0-10ppm
Note: the host closed, re-opening the power, oxygen, chlorine, nitrogen dioxide, sulfur dioxide and ammonia will take some time to stabilize.
Standard M20 terminal box
Anti-hydrocarbon (oil) vapor filter layer
SENSEPOINT sensor
M20 thread
shield
sensor serial number / date of manufacture
EXD / E waterproof connector
Technical parameters:
Operating temperature: -25 ℃ ~ + 50 ℃ humidity: 10-99% RH
preheating time: 3 minutes less than
response time: less than 5 seconds T20, T50 is less than 12 seconds, T90 is less than 30 s
power supply: DC 18V ~ 30V, the maximum power consumption of 0.9 watts
output: 4-20mA linearity error: less than 5% of full scale
sensor life: over two years
zero drift: time: less than + 2% of full scale / year
temperature: less than + 5% of full scale
humidity: less than + 2% of full scale
sensitivity drift: time: less than + 4% of full scale / year
temperature : less than 2% of full scale +
humidity: less than 2% of full scale +
sensor weight: 185 g Junction box Weight: about 0.5 kg
structural material: polyester shell preservative
Protection: Standard IP65
IP66 / 67 (installation of shields)
Ex certification:
the CE Certification: [ 123]
optional Accessories:
the weather baffle
calibration cover
fittings for wall mounting pipe
collection hood
Reviews