Category: the HONEYWELL gas detector Name: [ 123] the HONEYWELL gas detector model: Honeywell Optima Plus point infrared combustible gas detector [123 ] whether to recommend: is inventory: 111 [123 ] product description:

Honeywell HoneywellOptima Plus point infrared combustible gas detector

For over 50 years, “Sieger” has always been a world leader in the design and manufacture of gas detector device.

Typical Applications

offshore oil and gas platforms, Floating Production Storage and Offloading (FPSO) ship, tanker, Qizhan shore equipment, refineries, LNG / LPG bottling plants, gas compressor metering station, a gas turbine power plant, The solvent and spraying the printing apparatus.
Why Sieger searchpoint Optima Plus is the right choice
design has the advantage searchpoint Optima proven
have experience gained from more than 50,000 units worldwide installed Sieger searchpoint Optima Plus in
for development the latest technology and technical success Sieger open gas detector (Searchline Excel) of
with higher reliability ??
reliable operation (self-reported failure)
fast response
to reduce the routine maintenance [123 ] catalytic poison immunity
long life
can work
in an oxygen-free atmosphere Why searchpoint Optima Plus?
SoftwareTM more effectively prevent false alarms
with an optical device to warn the contamination, increase uptime
The dynamic heat controller ensures the condensing optic surface
No undetectable failure
improved fault diagnosis function
complete event record
low power consumption
has many hazardous area using the authentication
technical parameters
4mA to 20mA output type source and drain type output current (default source type)
to suppress 1mA 3mA (default 2mA)
warning 0 to 4mA (default 4mA)
0mA failure
overrange 21.5 mA to 20mA (21mA default)
select multiple digital output point Modbus RS485 (with intermediate DVC / DX100 (m) is connected to communicate)
Material 316 Stainless Steel
Accuracy
Optima Plus (HC) Zero <± 1% LEL, 50% FSD <± 2% LEL
Optima Plus (ET ) zero <± 2% LEL, 50% FSD <± 3% LEL
stressed accuracy LEL50% FSD at <± 2% LEL
linearity <5% FSD
response time T50 <4.5 seconds T90 <6.5 seconds (for methane, including weather shield) drift -40 ℃ to + 65 ℃
zero
generated through to the
time and temperature of the accreditation of the operating temperature -40 ℃ + 65 ℃ < ± 2% LEL
50% FSD at <± 4% LE
with the pressure oscillations 0.1% (reading) per mbar
power 18-32V (24V normal); 4.5W maximum
protection IP66 / 67
using a certified diagnostic manual operator to implement the operation